A closely stepped range of compressors for modern refrigeration, air conditioning and heat pump systems.
With its new BITZER ECOLINE series, BITZER offers high-efficiency universal compressors that satisfy the demands of modern refrigeration systems:extended range of applications
• Energy efficientcost-effective power regulation
• Wear-resistant drive mechanism
• Quiet and low-vibration
• Minimal space requirements
• Robust
BITZER ECOLINE compressors for operation with frequency inverters up to 70 Hz
All BITZER ECOLINE compressors are designed and optimised for 70 Hz operation. Depending on the refrigerant used and the environmental conditions, a compressor with a PW standard motor (400 V, 3-50 Hz) can be used, or a special motor (230V/400V, 3-50 Hz*) may be required and connected in a delta circuit (230 V, 3-50 Hz). The latter is the case for compressors using version 1 and 2 motors where they are to be operated throughout the entire documented area.
The use of a PW standard motor for 400 V or the connection of a 230/400 V motor in a star circuit must be discussed with BITZER on an individual basis due to the drop in the torque value when operating above 50 Hz see also Technical Information KT-420.
• Length: 309 mm
• Width: 457 mm
• Height: 352 mm
• CR Levels: 0.5
• Number of Cylinders: 4 pcs
• Refrigerant: R134a, R450A, R513A, R1234yf, R404A, R507A, R448A/R449A, R454C, R455A
• Motor Version: 1
• Series: CE3
• Starting Current (Locked Rotor): 82.4 A
• Supply voltage: 400/3/50 V/Ph/Hz
• Max. Operating Current: 16.5 A
• Max. Power Consumption: 8.9 kW
26.8 m3/h
• Discharge Line: 22.0 mm (7/8 inch)
• Suction Line: 28.00 mm (1 1/8 inch)
• Oil Charge: BSE32
• Option: BSE55 bei R134a, R450A, R513A, R1234yf tc > 70oC
• Oil Quantity: 2.00 l
Note 1: Data for 400 V/3/50 Hz with direct mains power supply. Observe the max. operation current / max. power input when selecting contactors, leads and fuses. Contactors: Category AC3. Use overcurrent relay to avoid exceeding max. operating current.Tolerance (�10%) based on the mean voltage range. Other voltages and current types on request220-240V ?/3Ph/50Hz - 380-420V Y/3Ph/50Hz265-290V ?/3Ph/60Hz - 440-480V Y/3Ph/60Hz
Note 2: Data for integration of the frequency converter (FC) � motor version 3 (R134a compressor): based on 400 V/3/50 Hz mains supply and use of 400 V/3/50 standard motor for FC operation up to 70 Hz. FC motor versions 1 and 2: Operation above 50 Hz anywhere within the operating area requires a special voltage motor