A closely stepped range of compressors for modern refrigeration, air conditioning and heat pump systems.
With its new BITZER ECOLINE series, BITZER offers high-efficiency universal compressors that satisfy the demands of modern refrigeration systems:extended range of applications
• Energy efficientcost-effective power regulation
• Wear-resistant drive mechanism
• Quiet and low-vibration
• Minimal space requirements
• Robust
BITZER ECOLINE compressors for operation with frequency inverters up to 70 Hz
All BITZER ECOLINE compressors are designed and optimised for 70 Hz operation. Depending on the refrigerant used and the environmental conditions, a compressor with a PW standard motor (400 V, 3-50 Hz) can be used, or a special motor (230V/400V, 3-50 Hz*) may be required and connected in a delta circuit (230 V, 3-50 Hz). The latter is the case for compressors using version 1 and 2 motors where they are to be operated throughout the entire documented area.
The use of a PW standard motor for 400 V or the connection of a 230/400 V motor in a star circuit must be discussed with BITZER on an individual basis due to the drop in the torque value when operating above 50 Hz see also Technical Information KT-420.
• Length: 303 mm
• Width: 633 mm
• Height: 385 mm
• CR Levels: 0.5
• Number of Cylinders: 4 pcs
• Refrigerant: R134a, R450A, R513A, R1234yf, R404A, R507A, R448A/RR455A, R407F
• Motor Version: 2
• Series: CE4
• Starting Current (Locked Rotor): 49.0 A
• Supply voltage: 400/3/50 V/Ph/Hz
• Max. Operating Current: 19.9 A
• Max. Power Consumption: 13.0 kW
41.3 m3/h
• Discharge Line: 28.0 mm (1 1/8 inch)
• Suction Line: 32.0 mm (1 3/8 inch)
• Oil Charge: BSE32
• Option: BSE55 bei R134a, R450A, R513A, R1234yf tc > 70oC
• Oil Quantity: 2.6 l
Note 1: Part winding motor Y/YY- 4VES-6Y .. 6FE-50Y wind distribution 50%/50%- 8GE-50Y .. 8FE-70Y wind distribution 60%/40%- Use motor contactors rated to about 60% of the max. operating current for PW start up design on request380-420V PW YY-3Ph-50Hz440-480V PW YY-3Ph-60Hz
Note 2: Data for integration of the frequency converter (FC) motor version 3 (R134a compressor): based on 400 V/3/50 Hz mains supply and use of 400 V/3/50 standard motor for FC operation up to 70 Hz. FC motor versions 1 and 2: Operation above 50 Hz anywhere within the operating area requires a special voltage motor.
Note 3: Data for 400 V/3/50 Hz with direct mains power supply. Observe the max. operation current / max. power input when selecting contactors, leads and fuses. Contactors: Category AC3. Use overcurrent relay to avoid exceeding max. operating current.
Accessory 1: Additional ventilator
Accessory 2: Check valve
Accessory 3: Control valve for power controller
Accessory 4: Control valve for unloaded start system
Accessory 5: Crankcase heater Refrigerator oil Unloaded start system
Accessory 6: Electronic oil level monitor without storage lid Refrigerant collector for RU
Accessory 7: IQ Module add-on Motor protection
Option: Refrigerator oil BSE55 with R134a, tc > 70 oC Pressurised gas temperature sensor RSK unit (Liquid receiver without compressor), Rail set top